For Four-way cassette
4.4 Convergent drainage
4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong.
4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.
4.4.3. Selecting the diameter
Number of connecting indoor unitsCalculate drainage volumeSelect the diameter
Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr)
集中排水管
Allowed volume(lean 1/50) (l/ hr) I.D. (mm) Thick
Hard PVC 14
25
3.0
Hard PVC
1488 30
3.5
Hard PVC
88334 40
4.0
Hard PVC
175334 50
4.5
Hard PVC
334 80
6.0
4.5 Drainage test
4.5.1Drainage without drain pump
After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows
smoothly.
4.5.2 Drainage with drain pump
Poke the Water Level Switch, remove the cover, use water pipe to pour 2000ml water i nto the water
receipt plate through the water inlet.
Turn on the power to Cooling operation. Check the pumps operation and switch on the Water Level
Switch. Check the pumps sound and look into the transparent hard pipe in the outlet at the same time to
check if the water can discharge normally.