d. Protection of pressure or temp.
e. Open-circuit and short-circuit trouble of T3
Is connection to connector of temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Is it the resistance is normal?
Indoor PCB is defective.
Replace the sensor
Yes
No
Protection of pressure or temp.
Is it k1 or K2 open ?
Is temp. protective switch K1 open
Possible reason
1. The wires is loose to K1
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is
defective
5. Outdoor unit is bad ventilation
6. Refrigerant is leakage
7. K1 switch is defective
Is pressure protective switch K2 open
Yes
Yes
Yes
Possible reason
1. The wires is loose to K2
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is
defective
5. Outdoor unit is bad ventilation
6. Refrigerant is two much
7. K2 switch is defective